BRK electronic Network Card ADF Adapter User Manual

INSTALLATION OF THE  
ADF ADAPTER PLUG  
ELECTRICAL SHOCK HAZARD. Turn off power to the area where you  
will install this unit at the circuit breaker or fuse box before beginning  
installation. Failure to turn off the power before installation may result in  
serious electrical shock, injury or death. Do not restore power until all  
Smoke Alarms are completely installed.  
Installation of this unit must conform to the electrical codes in your  
area; Article 760 of NFPA 70 (NEC), NFPA 72, NFPA 101; SBC (SBCCI);  
UBC (ICBO); NBC (BOCA); OTFDC (CABO), and any other local or  
building codes that may apply. Wiring and installation must be per-  
formed by a licensed electrician. Failure to follow these guidelines  
may result in injury or property damage.  
INSTALLATION INSTRUCTIONS  
This unit must be powered by a 24-hour, 120VAC pure sine wave 60Hz  
circuit. Be sure the circuit cannot be turned off by a switch, dimmer,  
or ground fault circuit interrupter. Failure to connect this unit to a  
24-hour circuit may prevent it from providing constant protection.  
1. Verify which MODELS are installed in your system to determine if they are  
compatible with the ADF Adapter Plug (see part C below).  
2. Turn off AC power.  
3. Remove unit. Remove old mounting bracket.  
4. Install new mounting bracket (see part A below).  
For all other Smoke Alarm information, instructions and warnings, refer  
to the Smoke Alarm User’s Manual.  
5. Connect the black end of the ADF Adapter Plug to the existing power  
connector (connect part C to part D as shown below).  
®
NOTE: There may not be enough room for the Adapter Plug and additional  
wiring to fit in the junction box. If not, the old power connector must be  
COMPATIBLE BRK MODELS  
®
®
®
All of the listed BRK and First Alert Alarms are compatible with the listed  
FIREX Alarms and will work with the enclosed Adapter Plugs.  
removed and replaced with a First Alert Power Connector.  
®
6. Connect the other end of the Adapter Plug to the appropriate Smoke Alarm  
®
BRK Alarms  
(connect part C to part B as shown below).  
4120, 9120 Series – AC, AC/DC Ion, Silence  
5919 – AC Photo  
7. Check all connections. Make sure all plugs are completely connected and  
snapped together. Ensure the Adapter Plug is securely connected to the  
existing Power Connector.  
2002RAC – AC/DC Photo  
7010 Series – AC, AC/DC Photo, Silence  
SC6120B, SC9120B – AC/DC Smoke/CO Combo  
HD6135FB – Heat Alarm  
8. Install the base of the Smoke Alarm to the mounting bracket.  
9. Restore power to the junction box.  
RM3 – Auxiliary Relay  
10. Test each Smoke Alarm. Press and hold the test button until the unit alarms.  
When testing a series of interconnected units you must test each unit  
individually. Make sure all units alarm when each one is tested.  
®
FIREX  
406 (Model #G-6) – AC Ion  
4518 (Model #ADC) – AC/DC Ion, Battery in Rear  
4618 (Model #FADC) – AC/DC Ion  
5000 (Model #FADC) – AC/DC Ion, Latching LED  
484 (Model #PG-40) – AC Photo  
4480 (Model #PAD) – AC/DC Photo  
5700 (Model #ADH) – Heat Alarm  
499 – Auxiliary Relay  
The Parts of This Installation  
D
A
Maximum of only 12 units (except model G-6) may be interconnected.  
A
B
Mounting Bracket  
Check for model numbers above.  
®
BRK 4120, 9120 Series  
Smoke Alarm  
®
Adapter Plug (ADF) Diagram for FIREX Models:  
C
D
ADF Adapter  
Plug Pin  
View  
Side View  
Existing compatible  
power connector  
White  
Orange  
Electrical Rating:  
120V AC, 100mA Maximum  
Black  
Not for Current Interruption  
C
NOTE: Twist tie should not be removed.  
®
NOTE: ADAPTER PLUG CANNOT BE USED TO CONNECT FIREX CARBON  
MONOXIDE ALARMS.  
®
B
THE ABOVE MODELS OF FIREX ARE THE ONLY MODELS THAT MAY BE  
INTERCONNECTED USING ONE OF THE ADAPTER PLUGS INCLUDED.  
IF THE MODEL IS NOT LISTED, IT MUST BE REMOVED FROM THE SYSTEM.  
NOTE:  
RECOGNIZED  
COMPONENT  
CONFORMS TO  
UL STANDARD 1977  
Independent evaluation of the  
Adapter Plug and interconnect  
compatibility was performed by  
Intertek, a division of ETL SEMKO.  
INCOMPATIBLE POWER CONNECTORS:  
DO NOT ATTEMPT  
INSTALLATION  
3055574  
© 2007 BRK Brands, Inc., a Jarden Corporation company (NYSE: JAH)  
3901 Liberty Street Road, Aurora, IL 60504-8122  
®
FIREX  
All rights reserved.  
US Patent No.: 6,641,433 B2  
BRK® is a registered trademark of BRK Brands, Inc.  
First Alert® is a registered trademark of the First Alert Trust.  
Firex® is a registered trademark of Maple Chase Company.  
®
NOTE: Adapter Plug can be used on FIREX Models manufactured on or  
before January 1, 2004.  
Printed in Mexico M08-0125-001  
H
06/07  
 

BenQ Projector PB9200 User Manual
Black Decker Food Processor FP1611SCKT User Manual
Breville Slow Cooker BSC400 User Manual
Califone DVD Player DVD105 User Manual
Canon Digital Camera 115 HS User Manual
Casio Cash Register QT 6000 User Manual
Casio Radio LK120 User Manual
Chamberlain Garage Door Opener WD962KEV User Manual
Chief Manufacturing Indoor Furnishings KSA 1020 User Manual
Cisco Systems Mobility Aid OL 27172 01 User Manual